Cali Energy research · Home batteries

How Many Cycles a Year Does a Home Battery Really Do? Measured on 28 Batteries in LA Homes

Home batteries in our Los Angeles monitoring fleet did a median 203 full-equivalent cycles over the past year — about 0.56 a day, not the one cycle a day that warranty and savings math often assume. Batteries set to work every day did a median 220; 6 of 28, almost all set to Full Backup, did fewer than the 52 a year the state’s SGIP incentive asks for. About 80% of the energy put in came back out, and a battery kept full for backup still drew about 1.5 kWh a day per 10 kWh of capacity. At the measured pace, 26 of 28 batteries would reach the end of their warranty term before any cycle or energy cap.

Updated October 15, 2026 · Data through October 2026 · Cali Energy research team · CSLB #1032379 · verify license

203
Full-equivalent cycles a year, median battery (220 among batteries that cycle)
0.56
Cycles a day, median battery
80%
Of the energy put in that came back out, batteries that cycle
6 of 28
Batteries below the SGIP minimum of 52 cycles a year

These are all 28 Enphase batteries in our monitoring fleet with at least 300 days of clean daily charge and discharge data in the past year, 21 of them with two or more years. A full-equivalent cycle is the battery’s usable capacity discharged once, whether in one evening or over several partial discharges: a 10 kWh battery that delivers 5 kWh a day does half a cycle a day.

About half a cycle a dayThe median battery did 203 cycles a year. Even batteries that worked daily averaged 0.6 of a full cycle, because most days they were not emptied.
The setting decidesBatteries now set to Full Backup did a median of about one cycle a year; self-consumption batteries 219.
About 20% does not come backBatteries that sat full for backup still drew about 1.5 kWh a day per 10 kWh of capacity; even part of that draw covers the gap between the datasheet and the meter.
The calendar runs out firstAt its measured pace the median battery would need 14 years to reach the strictest energy cap in Enphase’s battery warranties.

Cycles per battery

28 batteries, full-equivalent cycles over the past year.

Batteries by full-equivalent cycles a year
Number of batteries by cycles a year6 batteries did under 52 cycles; most did 150 to 250.024681012146under 52452–15012150–2504250–3002300 or more
Bars: number of batteries. A full-equivalent cycle = one usable capacity discharged. 52 a year is the SGIP minimum.
Batteries by cycles a year, with today’s operating mode
Cycles a yearBatteriesMode set today
under 52 (SGIP minimum)6full backup 5, self-consumption 1
52–1504savings 2, self-consumption 2
150–25012self-consumption 10, full backup 2
250–3004savings 2, self-consumption 1, AI optimisation 1
300 or more2savings 1, self-consumption 1
How to cite: Cali Energy, “How Many Cycles a Year Does a Home Battery Really Do?,” updated October 15, 2026, https://cali-energy.com/research/home-battery-cycles-per-year-los-angeles. Aggregated data are free to use under CC BY 4.0 with a link to this page.

Mode and utility

Median battery in each group, by its current operating mode.

Battery cycles by operating mode and utility
GroupBatteriesCycles a yearMiddle halfEnergy delivered a yearBelow 52 cycles
All batteries28203109–2342,307 kWh6
Mode today: self-consumption15219187–2302,460 kWh1
Mode today: savings5266132–2672,681 kWh0
Mode today: full backup710–958 kWh5
LADWP area818787–2202,299 kWh2
SCE area20218114–2402,307 kWh4

The operating mode explains most of the spread. Batteries set to store surplus solar and use it in the evening (self-consumption) did a median 219 cycles; those set to discharge in the expensive hours (savings) 266. Batteries set to Full Backup sit charged and wait for an outage: a median about one cycle. Two of the 7 now set to Full Backup cycled 188–217 times in the past year, so their setting most likely changed recently — a reminder that a mode chosen after an outage can quietly stay.

The utility made less difference than often assumed. LADWP-area batteries did a median 187 cycles and SCE-area batteries 218, even though LADWP still credits exports at the retail rate. The same pattern shows in home energy flows: see how much solar a home actually uses. How the modes work: how a home battery works.

Season by season

Batteries that cycle (100 or more a year): 21 batteries.

Full-equivalent cycles per day by month, batteries that cycle
Battery cycles per day by monthFrom 0.47 cycles a day in December to 0.72 in September.0.00.20.40.60.81.00.6Jan0.6Feb0.6Mar0.6Apr0.7May0.7Jun0.6Jul0.6Aug0.7Sep0.6Oct0.6Nov0.5Dec
Bars: median battery’s average cycles per day in each month, past 12 months.
Battery use by month, batteries that cycle
MonthCycles a day, median batteryDays with 80%+ of capacity discharged
January0.5718%
February0.5924%
March0.5725%
April0.6428%
May0.7030%
June0.6929%
July0.6133%
August0.5933%
September0.7230%
October0.6126%
November0.5622%
December0.4718%

Even the batteries that work every day rarely empty completely. In December the median one did 0.47 of a cycle a day, with a deep discharge (80% of capacity or more) on 18% of days; in late summer, when evenings are hot and the panels leave a surplus to store, 0.72 in September, with deep discharges on about a third of days in July and August. A battery sized on a June day will not fill the same way in December; see the battery sizing calculator.

How much energy comes back

Energy in and out, measured
MeasureValue
Energy delivered ÷ energy put in, batteries that cycle (median)80% (middle half 77–83%)
Standing draw of batteries kept full for backup (median of 5)15% of capacity a day, about 1.5 kWh for a 10 kWh battery
Datasheet round-trip efficiency, Enphase IQ Battery 10T89% (AC to battery to AC at 50% power)

Of every 100 kWh that went into the batteries that cycle, about 80 came back out. That is below the 89% Enphase lists for a single round trip, and the difference is mostly not the round trip. Batteries that sat full for backup and barely discharged still drew a median 1.5 kWh a day per 10 kWh of capacity — energy the battery takes just to stay ready, about 540 kWh a year. A cycling battery pays some of that cost too: for a 10 kWh battery moving a typical 6 kWh a day, about half that standing draw would be enough to account for the whole gap between 89% and what we measured.

For a backup-only battery that standing draw is the whole energy cost of keeping it ready; for a battery that cycles daily it is the price of shifting solar into the evening. Datasheet efficiencies of other brands are compared in how a home battery works.

Warranty headroom

Years each warranty cap would take at each battery’s measured pace.

Years to reach Enphase’s battery warranty caps at the measured pace
Warranty capFull-equivalent cyclesYears to reach it, median batteryBatteries reaching it within 10 yearsWithin 15 years
2.8 MWh per kWh of capacity (IQ Battery 3/10)about 2,800142 of 2817 of 28
4,000 discharged cycles (IQ Battery 3/10)4,000200 of 284 of 28
6,000 discharged cycles (IQ Battery 3T/10T, 5P, 10C)6,000300 of 280 of 28
Enphase Energy limited warranty, United States, effective July 1, 2023: IQ Battery 3/10 — 10 years, 4,000 discharged cycles or 2.8 MWh AC throughput per kWh of rated capacity, 70% capacity retained; IQ Battery 3T/10T — 15 years or 6,000 discharged cycles, 60% retained. Earlier editions apply to batteries activated earlier. Enphase does not say how partial discharges count toward cycles.

For almost every battery the calendar ends the warranty first. Under the strictest cap in Enphase’s US battery warranties, 2.8 MWh of energy per kWh of capacity, the median battery would need 14 years; only two of 28, both cycling more than 300 times a year, would reach it inside a 10-year term. The 4,000- and 6,000-cycle caps are further away still. What a warranty promises about capacity, and how other brands cap use, is in how long home batteries last.

The SGIP minimum and year-to-year changes

The state’s Self-Generation Incentive Program asks storage it pays for to deliver at least 52 full discharges a year, SCE’s program page says. Six of 28 batteries in our fleet did fewer in the past year, five of them set to Full Backup. What the program requires: SGIP battery incentives.

A battery’s pace also changes. Among 21 batteries with two or more full years, the median difference between their busiest and quietest year was 40 cycles, and three batteries spent a whole year almost idle (under 20 cycles) before or after a year of 100 or more. Checking the mode in the monitoring app once a season is the simplest way to catch a battery that has gone to sleep.

Even working batteries do not take a home off the grid: the battery homes we measured went without buying power on a median 0.4% of days. See what share of a home’s electricity solar covers.

Methodology

Batteries
All Enphase batteries in our monitoring fleet with at least 300 days of clean daily data in the past 365 days (27) or, failing that, in their latest calendar year (1): 28 batteries in 28 homes, 16 IQ Battery 3T, 9 IQ Battery 3 and 3 of the newer 5 kWh units. Most have 10.08 or 20.16 kWh of usable capacity.
Clean day
A day with a recorded charge or discharge (zero and zero means no data), not March 8, 2026 (a daylight-saving recording fault), and no more than two capacities of charge or discharge.
Cycles
Full-equivalent cycles = energy discharged ÷ usable capacity, scaled to 365 days.
Mode
The operating mode and settings on the export date, October 2026: self-consumption 15, full backup 7, savings 5, AI optimisation 1. Storm Guard was on for 15 and grid charging allowed for 19. Earlier settings are not recorded.
Energy returned
Discharge ÷ charge over the same days, batteries with 100 or more cycles a year. Charge includes any energy drawn from the grid.
Standing draw
Median daily charge, as a share of capacity, on days with almost no discharge, for the 5 batteries that did under 20 cycles a year.
Utility area
From California Energy Commission utility service-area maps, used only where the match is certain or highly likely.
Limits
28 batteries are a measured set, not a market sample, and all are Enphase. Capacity fade is not measured.

Sources: Cali Energy monitoring fleet (Enphase battery charge and discharge); Enphase Energy limited warranty for IQ Battery products, United States, effective July 1, 2023; Enphase IQ Battery 5P and 10C warranties; Enphase IQ Battery 10T data sheet; SCE Self-Generation Incentive Program page.

Frequently asked questions

How many cycles a year does a home battery do?

In our measured fleet, a median 203 full-equivalent cycles a year, about 0.56 a day. Batteries that cycle regularly did a median 220; batteries kept for backup did almost none.

Does a home battery do one full cycle a day?

Rarely. Even batteries that worked every day averaged 0.6 of a cycle, and discharged 80% or more of their capacity on only 16% of days.

How efficient are home batteries in real use?

About 80% of the energy put into the batteries that cycle came back out, against 89% on the IQ Battery 10T datasheet. Much of the gap is the standing draw a battery needs to stay ready: about 1.5 kWh a day per 10 kWh of capacity on batteries kept for backup.

Will I hit my battery warranty's cycle limit?

Unlikely. At the measured pace the median battery would need 14 years to reach the strictest Enphase cap; only 2 of 28 would reach it within 10 years.

Do LADWP batteries sit idle?

Not in our data. LADWP-area batteries did a median 187 cycles a year against 218 in SCE territory. The mode setting matters far more than the utility.

More research

Next steps

Adding a battery, or checking the one you have?

Prepared by Cali Energy, October 15, 2026. Figures describe systems in our monitoring fleet and are not a guarantee of what any specific roof will produce; orientation, tilt, shade, equipment and weather change results. Not engineering, financial or utility advice. See our Content Disclaimer.