ROOFING & SOLAR

The Cool-Roof Rule You Meet Only When You Re-Roof

There is a requirement in California's Energy Code that most homeowners never encounter until the moment they replace a roof — and then encounter as a surprise, usually after the color has already been chosen.

Updated September 1, 2026 · Last fact-checked September 1, 2026 · By the Cali Energy team · Northridge, CA · CSLB #1032379 (B, C-10, C-39) — verify license

It is the cool-roof rule, and its most counter-intuitive feature is this: it applies in more climate zones to a replacement roof than it does to a new house. A home built in 1968 in a zone where cool roofs were never required at construction can be held to the standard the day its roof is replaced.

This page sets out exactly where it applies, what it requires, who is exempt, and the several compliant ways out — including the ones that let you keep a dark roof.

The rule bites hardest on a replacement

California's prescriptive cool-roof requirements sit in Title 24, Part 6. Before the numbers, the trigger, because it governs everything below. Section 150.2(b)1I states that replacements of the exterior surface of an existing roof — including adding a new surface layer over the existing one — must meet Section 110.8 and the applicable subsections where more than 50 percent of the roof is being replaced.

So a spot repair or a partial replacement below that threshold does not pull the requirement in. A full tear-off, a full overlay, or any replacement covering more than half the roof does.

(For nonresidential and multifamily buildings the equivalent trigger is more than 50 percent of the roof area or more than 2,000 square feet, whichever is less — §141.0(b)2B and §180.2(b)1A. The 2,000 square-foot half of that test does not appear in the single-family section.)

With that threshold met, the prescriptive values are
SituationSectionSlopeClimate zonesAged solar reflectanceThermal emittanceSRI
New construction§150.1(c)11ASteep10–150.200.7516
New construction§150.1(c)11BLow13, 150.630.7575
Re-roofing — where >50 % of the roof is replaced§150.2(b)1IiSteep4, 8–150.200.7516
Re-roofing — where >50 % of the roof is replaced§150.2(b)1Iii(a)Low4, 6–150.630.7575

Read the climate-zone columns against each other. New construction on a pitched roof triggers in zones 10–15. A re-roof on the same pitched roof triggers in zones 4 and 8–15 — a wider net. For low-slope roofs the gap is wider still: two zones for new construction, ten for a re-roof.

The values themselves are aged values. That is a deliberate choice in the code: reflectance is measured after three years of field exposure by the Cool Roof Rating Council, or computed from the initial value using the CRRC's aged-value protocol, because real roofs collect dirt and lose reflectance. Products must be CRRC-rated and labeled, and the 2025 cycle moved SRI calculation onto ASTM E1980 (2019).

The prescriptive values for single-family did not change between the 2022 and 2025 code cycles — but the 2025 code took effect 1 January 2026, so a project permitted now is working from the current edition.

Nine out of ten of our roofs are in a triggering zone

The rule is only meaningful if you know which climate zone a house sits in — and this is where published advice tends to fall apart, because a search for "climate zone" returns USDA plant hardiness zones, a completely unrelated system used for gardening. We found sources confidently placing Palmdale and Northridge in the wrong Title 24 zones on exactly that confusion.

So we used the California Energy Commission's own file — Building Climate Zones by ZIP Code, 2,694 ZIPs — and joined it against our own project records. Of 365 completed installations with the roof covering recorded, 320 carried a ZIP we could match to a climate zone.

Where our work sits:

Climate zoneRoofsShare
CZ 924576 %
CZ 83811 %
CZ 6226 %
CZ 14103 %
CZ 1651 %

And what that means at re-roof time:

In a climate zone where the requirement can apply
Steep-slope roofs260 of 284 — 91 %
Low-slope roofs36 of 36 — 100 %

Of the records matched to a Title 24 climate zone, 260 of 284 steep-slope roofs and 36 of 36 low-slope roofs are located in zones where cool-roof requirements can apply when more than 50 percent of the roof is replaced. Project-specific exceptions and the performance-compliance path may still apply.

Read that carefully, because it is a statement about geography, not obligation. It says nine out of ten pitched roofs we have worked on sit in a zone where this rule is live — not that every one of them must carry a reflective covering. Whether it actually binds a given project depends on how much of the roof is being replaced, which of the four alternatives the building already satisfies, whether the assembly clears the weight exemption, and whether the design is being shown compliant through the performance path rather than the prescriptive one.

The exceptions are geographic and specific: the coastal CZ 6 strip — parts of Los Angeles nearer the ocean, Camarillo, part of Thousand Oaks, part of Long Beach — and mountain CZ 16, which takes in the higher parts of Santa Clarita.

Note the asymmetry there, because it catches people out. In coastal CZ 6, a steep-slope roof is outside the re-roof requirement while a low-slope roof on the same street is inside it. Zone 6 appears in the low-slope list (4, 6–15) and not in the steep-slope list (4, 8–15).

A caution about cities. A city is not a climate zone. Los Angeles spans zones 9, 8 and 6 in our own records; Santa Clarita spans 9 and 16; Long Beach spans 8 and 6. This has to be resolved by ZIP or address, not by city name — which is precisely why the CEC publishes a ZIP file and an address lookup tool.

The weight exemption — a threshold, not a material

There is an exemption that removes the requirement entirely, and it is widely misdescribed.

Roof constructions with a weight of at least 25 lb/ft² are exempt from the minimum requirements for aged solar reflectance and thermal emittance, or SRI.

That exemption appears against every one of the four rows in the table above — new construction and re-roof, steep and low.

It is stated as a weight threshold applying to the assembly, not as a material category. This distinction is not academic. It is common to read that "tile roofs are exempt," and that is not what the code says. Many tile assemblies do not reach 25 lb/ft²: the state's own Solar Permitting Guidebook assumes a tile roof assembly at 20 psf for structural screening purposes — below the exemption threshold. Lightweight concrete tile and a number of clay profiles fall short of 25; heavier profiles over solid sheathing can exceed it.

The honest instruction to a homeowner is therefore: the exemption exists, it is a number, and it applies to your specific assembly — have that weight established rather than assumed. A roofing contractor can give it from the product data and the deck build-up.

The other ways out

For a steep-slope re-roof, the code offers four alternatives treated as equivalent to a cool roof. Any one of them satisfies the requirement:

  • a. a ceiling assembly with a U-factor of 0.025 or lower, or insulated with at least R-38 ceiling insulation;
  • b. a radiant barrier in the attic — not installed directly above spaced sheathing, and meeting §150.1(c)2;
  • c. in Climate Zones 2, 4, 9, 10, 12 and 14 — buildings that have no ducts in the attic;
  • d. R-2 or greater continuous insulation above or below the roof deck.

The third one deserves more attention than it gets, because of where it applies. Climate Zone 9 covers most of the Los Angeles basin and San Fernando Valley — 76 percent of our own matched roofs sit in it. For a house in that zone with no HVAC ducts running through the attic, the cool-roof requirement is satisfied as the building already stands: no reflective product, no added insulation, no radiant barrier. Ducted attics are common in Los Angeles, so this will not apply to every house — but it is worth checking before assuming a light-colored roof is compulsory, and it is absent from most consumer guidance on this subject.

Note the limit of it, though. The duct alternative exists only in Climate Zones 2, 4, 9, 10, 12 and 14. A house in CZ 8 — which includes parts of Los Angeles, Long Beach and Lakewood — is subject to the requirement with no duct route available, and must use insulation, a radiant barrier or a compliant covering. The same is true in zones 11, 13 and 15.

The others are worth knowing too. If the attic is going to be insulated anyway — a common companion project to solar and electrification — the cool-roof requirement may already be satisfied by that work.

For low-slope re-roofs, the aged solar reflectance may alternatively be met using insulation at the roof deck per Table 150.2-B.

A note on partial work. Because the trigger is more than 50 percent of the roof being replaced, the scope of the job matters as much as the climate zone. Replacing one slope of a multi-plane roof, or repairing storm damage over part of the surface, may fall below the threshold. Where a project sits close to the line, the building department applying §150.2(b)1I is the authority on how the area is measured — ask before assuming either way.

There is one more exemption worth knowing, and it is solar-specific: building-integrated photovoltaic and building-integrated solar thermal panels are exempt, and on a re-roof the roof area covered by BIPV is not required to meet the reflectance minimums.

Note the limit of that. BIPV means the photovoltaic product is the roof covering — solar shingles and integrated panels, which the California Residential Code addresses separately in R905.15 and R905.16. A conventional rack-mounted array is not a roof covering; it sits above one. Rack-mounted panels do not exempt the roof beneath them.

Tile timing: the underlayment, not the tile

A tile roof raises a question that shingle roofs do not, and it is the reason this page matters to the 85 tile roofs in our own records.

Concrete and clay tile are extraordinarily durable — the covering can outlive the building's mortgage. The underlayment beneath it cannot. Felt underlayment is generally credited with something like 10 to 20 years of service under a covering; synthetic underlayments with roughly 20 to 35; rubberised asphalt with about 25 to 35. Those are industry and manufacturer ranges, not code figures, and they vary with ventilation and heat exposure — but the pattern holds regardless of the exact numbers: the tile is not what fails.

The code anticipates this. California Residential Code 2025, R908.5 provides that existing slate, clay or cement tile may be reinstalled — excluding any damaged, cracked or broken pieces, and requiring that rusted or deteriorated flashings, edgings, outlets and vents be replaced.

That single sentence is the legal basis for a lift-and-relay: the tile comes off, the underlayment beneath it is renewed, and the same tile goes back down. The roof is functionally new; the covering is the original.

Which sets up the sequencing problem. If a tile roof's underlayment is approaching the end of its life, that work is coming — and doing it after an array is installed means removing and reinstalling the array as well. This is the conversation to have before panels go on, not after, and it is a different conversation from the one about shingle wear, because the visible surface tells you almost nothing about the condition of what is underneath.

Sequencing: one decision, not three

If a re-roof is on the horizon for a house that is also considering solar, three questions that feel separate are really one:

  1. Cool-roof compliance — reflective covering, or one of the insulation alternatives, or a documented ≥25 lb/ft² assembly.
  2. Underlayment specification — which product, and what service life it buys relative to the array's 25 years.
  3. Array layout — decided against a roof that is about to change.

Taken together, these are resolved once. Taken separately, at least one of them is revisited at cost — usually the array, which has to come off so the layer underneath it can be dealt with.

Code references

Sections cited above, for readers who want to verify them directly in the code text.

  • California Residential Code 2025 (Title 24, Part 2.5), R908.5 — reinstallation of existing slate, clay or cement tile, excluding damaged pieces.
  • California Residential Code 2025, R905.15, R905.16 — BIPV shingles and BIPV roof panels as roof coverings.
  • Underlayment service-life figures are industry and manufacturer ranges, not code or standards values.

Frequently asked

Do I need a cool roof when I replace my roof in Los Angeles?

Often, but two things have to line up. The requirement is triggered where more than 50 percent of the roof is being replaced, and then it applies by climate zone — zones 4 and 8–15 for steep-slope roofs. Most of the LA basin and San Fernando Valley is zone 9. Of our own projects matched to a zone, 91 percent of steep-slope and 100 percent of low-slope roofs sit in zones where the rule can apply; the coastal CZ 6 strip and mountain CZ 16 are the local exceptions. Even then, four compliance alternatives, the weight exemption and the performance path may satisfy it without a reflective covering.

Are tile roofs exempt from the cool-roof requirement?

Not as a material. The exemption is for roof assemblies weighing 25 lb/ft² or more, whatever they are made of. Some tile assemblies clear that threshold and some do not — the state's structural guidebook assumes a tile roof at 20 psf, which is below it. Have the specific assembly weight established from the product data rather than assuming the exemption applies.

Can I avoid a cool roof another way?

Yes, on a steep-slope re-roof. Four alternatives are treated as equivalent: a ceiling U-factor of 0.025 or lower, R-38 or greater ceiling insulation, an attic radiant barrier, or R-2 or greater continuous insulation above or below the roof deck. Any one of them satisfies the requirement, so a dark roof remains possible.

Do solar panels exempt the roof underneath them?

Only building-integrated photovoltaics — products that serve as the roof covering itself. On a re-roof, the area covered by BIPV need not meet the reflectance minimums. A conventional rack-mounted array is not a covering and does not exempt the roof beneath it.

Should I re-roof before adding solar?

It depends on the remaining life of what is there, and on a tile roof that means the underlayment rather than the tile. If the covering or underlayment will need work during the array's 25-year life, doing it first avoids paying to remove and reinstall the system later.

What is an "aged" reflectance value?

The reflectance a product retains after three years of field exposure, measured by the Cool Roof Rating Council or computed under its aged-value protocol. The code uses aged rather than initial values because roofs accumulate dirt and weather, and a product's out-of-the-box reflectance is not what it delivers over its life.

Related reading

Sources & methodology

Two facts decide this for your house

Its Title 24 climate zone, and the weight of its roof assembly. We can establish both for a specific address and tell you which compliance route is cheapest for that roof.

Prepared by Cali Energy, September 1, 2026. This article is for general educational purposes only and is not legal, tax, financial, engineering, or utility advice. Rates, incentives, codes, permit requirements, equipment specifications, prices, and program terms may change; figures and timelines are estimates, not guarantees. Confirm current requirements with the applicable utility, AHJ, program administrator, manufacturer, or a licensed professional. See our Content Disclaimer. Cali Energy · 19201 Parthenia St, Unit E, Northridge, CA 91324 · CSLB #1032379 (B, C-10, C-39)